Wesley Crump at Practical Engineering walks through the reasons overhead power lines are held up by so many different kinds of structures. High voltage conductors are bare metal, so air is the insulation, and the tower is mostly the space that keeps the wires apart from each other, the ground and the steel. An arc needs roughly 20 to 30 kV per centimeter of air gap, so distribution lines at 10 to 35 kV need small insulators, while 500 kV lines need meters of clearance.
From there, the post covers the main tower families and the tradeoffs behind them: guyed towers are light and quick to build but take up a lot of land, H-frames are self-supporting and stay low for areas near airports, lattice towers balance footprint and material, and tubular monopoles use one foundation in tight rights-of-way.…