I have a backwater valve for the home. It was installed prior to me buying it, unsure when. I had a major flood where sewage backed up recently. Based on reports many people with back water valves had a sewage back up, likely due to the pressure.
Due to be flooded and the nightmare with insurance, I want to give myself as good of chances of mitigating it in the future. So I'm replacing it with an updated model ML-4TCA which has a manual operating switch.
Code in my area for 4" pipe is a 1% slope and the valves usually want 2% slope for them.
I broke out concrete and excavated the existing system. There is a connection that goes to the basement bathroom. I measured the small piece of ABS on the house side of the valve to be 1.25% downward, but then the valve and the sewer side ABS was 2.15% slope in the wrong direction!…